A few weeks ago a customer inquired whether we provide test leads to go with our PAT Testers to test Fixed Appliances. When we asked why he wanted to do this, he said he had been advised to do this on a course based around the 4th Edition of the IET COP.
This post tries to put the record straight.
This post tries to put the record straight.
A search in Google brought up some promotional material for the Apollo 600 which stated:
"The new IET Code of Practice recognises that the inspection and testing of appliances such as hot air hand dryers and water boilers can be more complex than portable and non-fixed equipment but this does not mean that only visual inspections are required."
This I thought was the most likely source of this information.
I was quite surprised about this and dusted off my copy of the IET Code of Practice to have another look. This says that for offices and schools, the period between testing is 4 years. It also says that the period between testing can be relaxed based on a risk assessment.
This means that if the risk assessment leads to the conclusion that only a Formal Visual Inspection is required then testing does not need to be carried out. As fixed appliances are not moved regularly there is little risk of damage to power cables.
Summary
Providing leads with a PAT tester to carry out testing on Fixed Electrical Appliances is quite unnecessary.
First of all when PAT testing is based on the actual risks posed, often there is no need for any PAT testing of these appliances.
Secondly, inviting users to test fixed electrical appliances, can be quite dangerous - especially when it is not necessary.
Note
The Health and Safety Executive say the following in their myth buster section.